Straight Run Requirements of Various Flow Technologies

Straight Run Requirements of Flow Technologies

Straight runs refer to the distance of straight piping required before the inlet or after the outlet of a flow meter. Straight-run is one of the most significant variables to consider in your flow meter installation to ensure accurate and repeatable flow measurement. All flow technologies have recommended installation and engineering practices to ensure they meet their published specifications and for optimal performance, accuracy and repeatability. Flow meter users are frequently challenged with wide variations in their actual field conditions and installation constraints that are much different from the ideal conditions under which their flow meter was calibrated. Inadequate straight-run or the presence of flow disrupters are the most common real world constraints to proper flow meter installation.

ข้อกำหนดของการเดินท่อตรงของเครื่องวัดอัตราการไหล

การเดินท่อตรงหรือสเทรทรัน (Straight Run)

This guide provides straight run requirements of various flowmeter and transmitters that SmartMeasurement  :

Flow Technology

Elbows

Reduction

Expanding

After Valves

Before Valves

After Pump

Before Pump

ALMAG Magnetic

5D up, 3D down 5D up, 3D down 10D up, 3D down 10D up, 3D down 5D up, 3D down 15D up, 3D down Not allowed

ATMF Thermal Mass

10~20D up, 5D down 10D up, 5D down 20D up, 5D down 50D up, 5D down 10D up, 10D down 50D up, 5D down 10D up, 20D down

ALCM Coriolis Mass

Not needed Not needed Not needed Not needed Not needed Not needed Not needed

ALSONIC Ultrasonic

10D up, 5D down 10D up, 5D down 30D up, 5D down 30D up, 5D down 10D up, 10D down 50D up, 5D down 10D up, 15D down

ALPD Positive Displacement

Not needed Not needed Not needed Not needed Not needed Not needed Not allowed

ALTM Turbine

20~40D up, 5D down 20D up, 5D down 15D up, 5D down 25~50D up, 5D down 10D up, 10D down 50D up, 5D down Not allowed

ALVAMT Variable Area

5D up, 1D down 5D up, 1D down 5D up, 2D down 10D up, 1D down 5D up, 5D down 15D up, 1D down Not allowed

ALDP  Differential Pressure (DP) Meters

5D up, 2D down 5D up, 2D down 5D up, 2D down 10D up, 2D down 5D up, 5D down 15D up, 2D down Not allowed

ALVT Vortex

25~50D up, 5D down 15D up, 5D down 25D up, 5D down 25D up, 5D down 10D up, 15D down 40D up, 5D down Not allowed

ALDPT Pressure Transmitter

Not needed Not needed Not needed Not needed Not needed Not needed Not needed
** ACONE is used for ALDP Differential Pressure Flow Meters

Smart Solutions with SmartMeasurement™

Reference: SmartMeasurement