Straight Run Requirements of Flow Technologies
Straight runs refer to the distance of straight piping required before the inlet or after the outlet of a flow meter. Straight-run is one of the most significant variables to consider in your flow meter installation to ensure accurate and repeatable flow measurement. All flow technologies have recommended installation and engineering practices to ensure they meet their published specifications and for optimal performance, accuracy and repeatability. Flow meter users are frequently challenged with wide variations in their actual field conditions and installation constraints that are much different from the ideal conditions under which their flow meter was calibrated. Inadequate straight-run or the presence of flow disrupters are the most common real world constraints to proper flow meter installation.
ข้อกำหนดของการเดินท่อตรงของเครื่องวัดอัตราการไหล
การเดินท่อตรงหรือสเทรทรัน (Straight Run)
This guide provides straight run requirements of various flowmeter and transmitters that SmartMeasurement :
Flow Technology |
Elbows |
Reduction |
Expanding |
After Valves |
Before Valves |
After Pump |
Before Pump |
ALMAG Magnetic |
5D up, 3D down | 5D up, 3D down | 10D up, 3D down | 10D up, 3D down | 5D up, 3D down | 15D up, 3D down | Not allowed |
ATMF Thermal Mass |
10~20D up, 5D down | 10D up, 5D down | 20D up, 5D down | 50D up, 5D down | 10D up, 10D down | 50D up, 5D down | 10D up, 20D down |
ALCM Coriolis Mass |
Not needed | Not needed | Not needed | Not needed | Not needed | Not needed | Not needed |
ALSONIC Ultrasonic |
10D up, 5D down | 10D up, 5D down | 30D up, 5D down | 30D up, 5D down | 10D up, 10D down | 50D up, 5D down | 10D up, 15D down |
ALPD Positive Displacement |
Not needed | Not needed | Not needed | Not needed | Not needed | Not needed | Not allowed |
ALTM Turbine |
20~40D up, 5D down | 20D up, 5D down | 15D up, 5D down | 25~50D up, 5D down | 10D up, 10D down | 50D up, 5D down | Not allowed |
ALVAMT Variable Area |
5D up, 1D down | 5D up, 1D down | 5D up, 2D down | 10D up, 1D down | 5D up, 5D down | 15D up, 1D down | Not allowed |
ALDP Differential Pressure (DP) Meters |
5D up, 2D down | 5D up, 2D down | 5D up, 2D down | 10D up, 2D down | 5D up, 5D down | 15D up, 2D down | Not allowed |
ALVT Vortex |
25~50D up, 5D down | 15D up, 5D down | 25D up, 5D down | 25D up, 5D down | 10D up, 15D down | 40D up, 5D down | Not allowed |
ALDPT Pressure Transmitter |
Not needed | Not needed | Not needed | Not needed | Not needed | Not needed | Not needed |
** ACONE is used for ALDP Differential Pressure Flow Meters
Smart Solutions with SmartMeasurement™
Reference: SmartMeasurement