DOWNLOAD CATALOG (ดาวน์โหลดแคตตาล็อก)
FineTek TXX2 Explosion-proof Safety Barrier Operations Manual |
FineTek TXX2 Explosion-proof Safety Barrier Operations
The barrier is provided to isolate the power supply of a transmitter in a hazardous area, as well as transmit analog signal and digital signal generated by the transmitter to the safe side. The analog 4~20mA output signal can be converted into a 4~20mA isolated type. Moreover, it can read the HART digital signal or RS485 signal in the hazardous side, and isolates the digital output signal to the safe side.
-
Wide input voltage range
-
Integrated power supply safety barrier and digital communication safety barrier
-
Insulation withstand voltage of up to 2500V R in hazardous and safe sides
-
RS485 repeater mode for safety digital communication
-
HART repeater mode for safety digital communication
-
Internal 250 Ohm for HART communication
-
Power supply indicator and digital communication indicator
-
Intrinsically safe explosion-proof IECEx/ATEX
Hazardous side | |
Input Current | 4~20mA or 20~4mA |
Voltage | <35 Vdc |
Digital output | HART/RS485 |
Safe side | |
Supply voltage | 20~35Vdc |
Power consumption | 4W |
Analog output | 4~20 mA (active), Load impedance <500W |
Digital output | HART 7.3(Internal 250W communication resistance) RS485 |
Technical parameters | |
Accuracy | 0.1% F.S(20°C) <2.0uA / °C(25°C~60°C) <3.0uA / °C(-20°C~25°C) |
Ambient temperature | -20~60°C |
Insulation strength | 2500Vac; Leakage current <1mA; 1min, Hazardous side and safe side |
IP grade | IP20 |
Application environment | Zone 0, Zone 1, Zone 2、 IIA、IIB/IIIC、IIC |
Certification (Optional) | IECEx/ATEX |
สอบถามข้อมูลเพิ่มเติม ติดต่อเรา :
02-384-6060 (อัตโนมัติ) [email protected] บริษัท ฟลูเทค จำกัด Flu-tech @flutech.co.th