FineTek TXX2 Explosion-proof Safety Barrier Operations
The barrier is provided to isolate the power supply of a transmitter in a hazardous area, as well as transmit analog signal and digital signal generated by the transmitter to the safe side. The analog 4~20mA output signal can be converted into a 4~20mA isolated type. Moreover, it can read the HART digital signal or RS485 signal in the hazardous side, and isolates the digital output signal to the safe side.
DOWNLOAD CATALOG (ดาวน์โหลดแคตตาล็อก)
Features
-
Wide input voltage range
-
Integrated power supply safety barrier and digital communication safety barrier
-
Insulation withstand voltage of up to 2500V R in hazardous and safe sides
-
RS485 repeater mode for safety digital communication
-
HART repeater mode for safety digital communication
-
Internal 250 Ohm for HART communication
-
Power supply indicator and digital communication indicator
-
Intrinsically safe explosion-proof IECEx/ATEX
SPECIFICATIONS
Hazardous side | |
Input Current | 4~20mA or 20~4mA |
Voltage | <35 Vdc |
Digital output | HART/RS485 |
Safe side | |
Supply voltage | 20~35Vdc |
Power consumption | 4W |
Analog output | 4~20 mA (active), Load impedance <500W |
Digital output | HART 7.3(Internal 250W communication resistance) RS485 |
Technical parameters | |
Accuracy | 0.1% F.S(20°C) <2.0uA / °C(25°C~60°C) <3.0uA / °C(-20°C~25°C) |
Ambient temperature | -20~60°C |
Insulation strength | 2500Vac; Leakage current <1mA; 1min, Hazardous side and safe side |
IP grade | IP20 |
Application environment | Zone 0, Zone 1, Zone 2、 IIA、IIB/IIIC、IIC |
Certification (Optional) | IECEx/ATEX |