Digital electropneumatic positioner for the integrated mounting on process control valves
BURKERT – TYPE 8696 Compact positioner for integrated mounting on pneumatically operated process valves. Remote setpoint adjustment via a 4-20 mA signal. A contact-free continuous sensor measures the position of the valve spindle. Simple installation through automatic TUNE-Function and setting through DIP-switch: Close tight function, Characteristic curves selection, Reversal of effective direction, Switching manual /automatic operation, Binary input. A software interface can be used for, amongst others, linearisation of the operation characteristics by using free programmable fixed points. The valve position indication is shown through LED components. As an option an analogue position feedback can be integrated.
DOWNLOAD CATALOG (ดาวน์โหลดแคตตาล็อก)
BURKERT TYPE 8696 สามารถใช้ได้ร่วมกับ
General Technical Data | Burkert - Type 8696
Product features |
|
Dimensions | Detailed information can be found in chapter “3. Dimensions” on page 6. |
Body | PPS, Stainless steel |
Seals | EPDM |
Cover | PC |
Operating keys | 2 |
DIP switch | Integrated (only for 24 V DC version without digital communication) |
Service-interface | Connection with PC via USB connection |
Configuration tool | Bürkert Communicator PACTware (only for 24 V DC device version with serial interface) |
Initialization positioner | Automatic by X.TUNE function (automatic adjustment of the positioner) |
Manual override pilot valve | In manual mode via operating keys |
Display of device and valve status | Multicoloured LEDs |
Digital | IO-Link, Bürkert system bus (based on CANopen) |
Position sensor |
|
Measuring principle | Inductive |
Position detection module | Contactless (wear-free) analogue position sensor |
Stroke range Valve spindle | 3…32 mm |
Electrical data |
|
Operating voltage | 24 V DC ± 10 % UL: NEC Class 2 |
Residual ripple | 3 acc. to DIN EN 61140 |
Protection class | 10 % |
Power consumption | < 3.5 W |
Input /Output |
|
Digital input | 1 binary input |
Analogue output | 1 analogue output (optional) 4…20 mA, 0…20 mA |
Electrical connection | |
Multipole version | M12, 8- resp. 5 pin acc. to device version (see “4. Device/Process connections” on page 7) |
Pneumatic data |
|
Control medium | Neutral gases, air, quality class acc. to ISO 8573 – 1 |
Dust content | Class 7 (< 40 µm particle size) |
Particle density | Class 5 (< 10 mg/m3) |
Pressure dew point | Class 3 (<- 20 °C) |
Oil content | Class X (< 25 mg/m3) |
Supply pressure | 0…7 bar1.) |
Pilot air ports | Threaded connection G â…›, stainless steel |
Positioning system (control function and air capacity) |
|
Single-acting | 7 lN/min for aeration and ventilation (QNn value acc. to definition at pressure drop from 7 to 6 bar absolute) |
Actuator series/size | Type 23xx, Ø actuator 50 mm Type 2103, Ø actuator 50 mm |
*For selecting the correct product please refer to the technical data, images and notes for proper use according to the data sheet, or contact Flu-Tech directly.
สอบถามข้อมูลเพิ่มเติม ติดต่อเรา :
02-384-6060 (อัตโนมัติ) [email protected] บริษัท ฟลูเทค จำกัด Flu-tech @flutech.co.th