2/2 way ball valves with electrically driven actuator
The motorized ball valve Type 2664 consists of a brass or stainless steel body and a motor drive with manual override and optical position indicator. The motor drive is connected to the ball valve via the mechanical interface F03 according to DIN ISO 5211. The ball valve works according to 2-position operation. The voltage is switched using a cam disc and two microswitches. The motor drive moves the ball valve by 90° and thus opens or closes the line cross-section. In the version with a potentiometer, specified intermediate positions are possible. Microswitches or potentiometers can also be used for electrical position feedback. The valve body is supplied in two or three parts. With the three-part design, the center part of the ball valve can be easily removed from the system.
DOWNLOAD CATALOG (ดาวน์โหลดแคตตาล็อก)
General Technical Data
Housing material |
MS nickel-plated or VA 1.4408 |
Motor drive material |
PA |
Sealing material |
PTFE |
Media |
Gaseous and liquid (Media that do not harm housing and sealing materials) |
Media temperature |
0 to +80 °C |
Ambient temperature |
0 to +50 °C |
Viscosity line connection |
Max. 40 mm2/s
|
Line connection |
G 1/4 bis G 1
|
Housing type |
2-part or 3-part |
Housing design |
Manual override and optical position indicator |
Operating voltage |
24 V DC or 230 V AC |
Voltage tolerance |
±10 %
|
Power consumption |
5,5 W oder 2,3 W
|
Rated current |
230 mA at 24 V DC 10 mA at 230 V AC |
Motor voltage |
24 V DC ± 10% |
Drive torque |
9 Nm at 24 V DC |
Nominal operating mode |
Intermittent duty ED 50% (cycle time 5 min) |
Setting direction |
Adjustable with polarity |
Actuating time for 90° |
14 s |
Electrical connection |
7-pin circular connector according to DIN 43651 |
Motor drive design |
With microswitches or potentiometer 1 kΩ |
Degree of protection |
IP 65 with junction box |
Mounting position |
Any, preferably in an upright position |
Connection drive with ball valve |
Interface F03 according to DIN ISO 5211, 9 mm |
Pressure specifications [bar] |
Overpressure to atmospheric pressure |