RTD temperature sensor with CANopen interface
Resistance thermometers are the preferred choice for measuring the temperature of liquids and gases. The design offers reliable tightness under negative and positive pressure.
The measuring insert is equipped with a Pt1000 temperature sensor according to DIN EN 60751, Class A. The measured temperature value is digitised, linearised and made available via the CANopen digital communication interface (CAN slave) for further processing.
Instead of an analogue output, this device offers the CANopen digital interface. This allows bidirectional data transfer, e.g. with a CAN/Ethernet gateway or directly to a PLC that is equipped with a CAN interface. CAN devices can also be connected to the Bürkert büS digital communication interface. A driver used for data exchange and settings of the 8412 is integrated in the Bürkert PC tool Communicator.
Several useful auxiliary functions have been implemented through the DS 404 device profile.
DOWNLOAD CATALOG (ดาวน์โหลดแคตตาล็อก)
BURKERT TYPE 8412 สามารถใช้ได้ร่วมกับ
General Technical Data
Product properties |
|
Material | |
Non wetted parts | |
Housing | Stainless steel 1.4571 (316Ti) |
Wetted parts | |
Process connection | Stainless steel 1.4571 (316Ti) |
Protection tube | Stainless steel 1.4571 (316Ti) |
Dimensions | Detailed information can be found in chapter “3. Dimensions” on page 5. |
Measurement element | Pt1000 temperature sensor, two-wire circuit |
Probe length | 50 or 100 mm |
Measuring range | – 50…+ 150 °C (- 58…+ 302 °F) |
Monitoring | • Measuring circuit – Underrange (freely selectable lower limit) – Overrange (freely selectable upper limit) • Probe short circuit • Probe break |
Additional functions | • Min./max. measured value memory • Fine adjustment • Toggling between °C, °F, °K • Decimal places selectable 0, 1, 2 |
Weight | Approx. 80 g for the version with thread connection and 100 mm probe length. The weight of the temperature sensor depends on the process connection and the inser-tion length. |
Performance data |
|
Sampling rate | 250 ms |
Transmission behaviour | Temperature linear |
Response time | • t0.5 = 5 s; t0.9 = 12 s, in water with a flow velocity of 0.4 m/s • t0.5 = 40 s; t0.9 = 110 s, in air with a flow velocity of 3.0 m/s |
Measuring resolution | 12 Bit |
Measurement deviation | • Tolerance class A according to EN 60751:2009 / IEC 60751:2008 • Max. ± 0.2 % of the measuring range span |
Electrical data |
|
Operating voltage | 10…30 V DC, filtered and regulated |
Power source (not supplied) | The auxiliary energy of the pressure sensor must meet SELV requirements; optionally, an energy-limited current circuit according to section 9.3 of DIN EN 31010-1 and UL 61010-1 can be used. |
Current consumption | Approx. max. 45 mA |
DC reverse polarity protection | Yes |
Overvoltage protection | Yes |
Short circuit protection | Yes |
Cable | 5-wire shielded cable, length depends on the transmission speed. The physical CAN transmission is standardized according to ISO 11898‑2 (high‑speed) and ISO 11898‑3 (low-speed) |
Medium data |
|
Fluid | Liquid and gaseous medium |
Process/Port connection & communication |
|
Process connection | G ½” or NPT ½” screw‑in thread |
Electrical connection | M12 × 1 male connector, 5 pin according to DIN IEC 60947‑5‑2 |
Digital communication: CANopen | |
Protocol | CiA DS 301, V4.02, CANopen slave |
Profile | CiA DS 404, V1.2; measuring devices and closed‑loop controllers |
Baud rate | 20 kbaud to 1 Mbaud, setting via LSS or SDO |
Node ID | 1 to 127 setting via LSS or SDO |
PDO | 0 Rx, 1 Tx |
Fluid pressure | Max. 40 bar |
SDO | 1 Rx, 1 Tx |
Emergency | Yes |
Heartbeat | Yes (if active, then Node Guarding deactivated) |
Node Guarding | Yes (if active, then Heartbeat deactivated) |
LSS | Yes |
SYNC | Yes |
Operation and project planning | All parameters are accessible via the CANopen object directory (EDS) and can be set via standard CANopen software tools or Bürkert Communicator. |
EDS (electronic data sheet) | • Device driver in Bürkert Communicator tool Type 8920, see “Bürkert Communicator” on the website in the Software chapter Type 8920 • See “Device Description Files” on the website in the Software chapter Type 8412 |
Factory setting | See “Operating Instructions Type 8412“ on the website in the User Manuals chapter Type 8412 |
Approvals and certificates |
|
Standards | |
Degree of protection | IP67, according to IEC/EN 60529 with female connector screwed on |
Accuracy class | Class A according to IEC 60751 |
Protection class | Class III according to EN 61140 |
Directives | |
CE directives | The applied standards, which verify conformity with the EU Directives, can be found on the EU Type Examination Certificate and/or the EU Declaration of conformity (if applicable) |
Electromagnetic compatibility (EMC) | Electromagnetic compatibility (EMC) • Interference emission: class B • Immunity to interference: to industrial requirements |
Pressure equipment directives | • The device does not meet the requirements for “safety accessories” within the meaning of the Pressure Equipment Directive 2014/68/EU. • Complying with Article 4, Paragraph 1 of 2014/68/EU directive Detailed information on the pressure equipment directive can be found in chapter “2.1. Pressure Equipment Directive” on page 5. |
Environment and installation |
|
Ambient temperature | |
Operation | – 20…+ 85 °C (- 4…+ 185 °F) |
Storage | -40…+ 85 °C (- 40…+ 185 °F) |
Temperature influence | ≤ ± 0.0025 % of the measuring span per K deviation from 22 °C |
Relative air humidity | • During operation: ≤ 100 %, without condensation on the outer housing surface of the device • During storage: ≤ 90 %, without condensation |
Climate class | 3K7 according to EN 60721‑3‑3 |
Area of use | Indoors and outdoors (protect this device against electromagnetic interference, ultraviolet rays and the effects of climatic conditions) |
Vibration resistance | According to EN 60068‑2‑6: • for 50 mm probe length: 10 g max. with 10…2000 Hz • for 100 mm probe length: 5 g max. with 10…300 Hz |
Shock resistance | According to EN 60068‑2‑27: • for 50 mm probe length: 50 g, 3 ms • for 100 mm probe length: 30 g, 3 ms |
Mounting position | Installation: unrestricted |
*For selecting thecorrect product please refer to the technical data, images and notes for proper use according to the data sheet, or contact Flu-Tech directly.